Eight Zone Panel

  • Complete Analog Solid-State and modular
    in type.
  • Two wire operation for Detector and Manual
    Call Point.
  • Facility to connect stand by supply or battery
    backup.
  • Panel compatible for detectors manufactured
    by most of the International Manufactures.
  • Facility (optional) for interlooping with Halon / Co2 / FM200 gas system.
  • Audio and Visual alarm for all signals which is being monitored by control panels.
  • Facility to shutdown auxiliary units in case of FIRE.
  • Automatic changeover from AC Mains supply to standby supply, in case of AC Mains fail.
  • Individual zone ISOLATE facility.
  • Test facility provided for FIRE & FAULT (Open / Short).
  • Facility to connect external sounder in each zone.
  • Two stage general alarm :
        1. Intermittent tone for FIRE.
        2. Single tone for FAULT.
  • Automatic battery charging facility for battery backup.
  • Facility (optional) to connect Public Address System & Talk Back.
SPECIFICATION
MECHANICAL SPECIFICATION
  • MATERIAL
  • : 16 SWG Sheet Metal.
  • DIMENSION
  • : 280 mm X 275 mm X 200 mm (W x H x D)
    Dimension may vary as per number of zones.
    (Given dimension is for up to 8 Zones).
  • COLOUR
  • : Fire Red / Siemens Gray.
  • MOUNTING
  • : Wall mounting, Top cable entry.
    ELECTRICAL SPECIFICATION
  • WORKING VOLTAGE
  • : 240 VAC. ± 10% (Mains supply)24 VDC. ± 10% (Standby supply)
  • POWER CONSUMPTIONS
  • : 40 Watts in quiescent condition
  • POWER CONSUMPTION
  • : 20Watts.
    ZONE CURRENT
  • In Normal Condition
  • : 6 TO 7 mA With 4K7 End Of Line Resistance
  • In Fire Condition
  • : 45 to 70 mA per zone
  • In Short Condition
  • : 50 to 60 mA per zone
  • Max O/P current for External Zonal     Hooter
  • : 300 mA per zone
  • Potential free Common Fire Relay C/O     Contact
  • : 230 VAC. 5A. Max. per 1 Set